• Frequency Input: 0-100 Hz to 0-30 kHz
• DC Output: 0-1 V, 0-5 V, 0-10 V, +/- 5 V, +/- 10 V, 4-20 mA, etc.
• Field-Configurable by User
The APD 7580 accepts a frequency input and provides an optically isolated DC voltage or current output that is linearly related to the input.
Common applications include frequency to DC conversions from frequency output type devices such as rotary encoders, magnetic pick-ups, proximity sensors, variable speed drives, and flow meters. For PLCs that do not have analog outputs, often the pulse rate of a discreet output can be programmed to vary. By connecting the APD 7580 to this output, a proportional analog signal can be generated. A 15 VDC power supply is provided to power the sensor input, if required.
Full 3-way isolation (input, output, power) makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction.
The APD 7580 input and output can be field-configured via external rotary and slide switches. Common ranges are on the module label. Many additional combinations are possible. Consult the factory for assistance with special ranges.
Options:
TECHNICAL SPECIFICATIONS
Input
Field Rangeable; Via external rotary & slide switches
Frequency Input: 0-100 Hz to 0-30 kHz
Output
Field Rangeable; Via external rotary & slide switches
Voltage: 0-1 VDC to 0-10 VDC
or
Bipolar Voltage: +/- 1 VDC to +/- 10 VDC
or
Current (20 V compliance): 0-1 mADC to 0-20 mADC
Isolation
Full 1200 Vrms Input/Output/Power Isolation
Features
1 Minute Setup for 30 Input & 18 Output Ranges
External Switches & Tables for Range Selection
Removable Plugs for Faster Installation
Full 1200 V Input/Output/Power Isolation
Input and Output LoopTracker® LEDs
Output Test Button
Built-In Loop Power Supply for Sink/Source Output
Applications
Monitor & Control Motor or Line Speed
Convert a Square Wave Output to 4-20 mA Simplify Interfacing of Frequency Type Devices